دانلود مقاله ISI انگلیسی شماره 63948
ترجمه فارسی عنوان مقاله

استخر شنا به عنوان غرق گرما برای تهویه هوا: تجزیه و تحلیل امکان فنی در کالیفرنیا

عنوان انگلیسی
Swimming pools as heat sinks for air conditioners: California feasibility analysis
کد مقاله سال انتشار تعداد صفحات مقاله انگلیسی
63948 2013 13 صفحه PDF
منبع

Publisher : Elsevier - Science Direct (الزویر - ساینس دایرکت)

Journal : Energy and Buildings, Volume 59, April 2013, Pages 252–264

ترجمه کلمات کلیدی
استخر، تهویه مطبوع، سینک حرارتی، بهره وری انرژی، مدل حرارتی، اعتبار تجربی، مدلسازی انرژی، ابزار طراحی
کلمات کلیدی انگلیسی
Swimming pool; Air conditioning; Heat sink; Energy efficiency; Thermal model; Experimental validation; Energy modeling; Design tool

چکیده انگلیسی

Earlier studies used field testing of swimming pool temperatures to validate a mathematical model for predicting the temperature of an unheated pool. Combining those results with manufacturers’ data on the performance of vapor-compression air conditioners as a function of heat rejection temperature, the analyses in the paper suggest that rejecting air conditioning heat to a swimming pool can save approximately 25–30% of single-family residential cooling electricity use and reduce cooling electricity demand during peak conditions by 30–35%, as compared to using the same compressor to reject the heat to ambient air. The savings is expected to vary depending on the severity of the climate, as well as the pool temperature experienced during the summer. The original model was refined so as to accommodate air-conditioner heat rejection to predict pool temperatures based on weather data, pool size, shading of the pool, and air-conditioner heat rejection to the pool. The results of an experimental validation of the augmented pool thermal model are presented here. In addition, the model of a pool-coupled air conditioning system was used to develop a design tool for determining the pool size needed to absorb realistic heat rejection from air conditioners in various California climate zones.