دانلود مقاله ISI انگلیسی شماره 6355
ترجمه فارسی عنوان مقاله

تجزیه و تحلیل پارامترهای مصرف انرژی ساختمان و اندازه گیری صرفه جویی در انرژی و تایید با استفاده از نرم افزار eQUEST

عنوان انگلیسی
Analysis of building energy consumption parameters and energy savings measurement and verification by applying eQUEST software
کد مقاله سال انتشار تعداد صفحات مقاله انگلیسی
6355 2013 8 صفحه PDF
منبع

Publisher : Elsevier - Science Direct (الزویر - ساینس دایرکت)

Journal : Energy and Buildings, Volume 61, June 2013, Pages 100–107

ترجمه کلمات کلیدی
( - ((& - صرفه جویی در مصرف انرژی و اجرای قرارداد () - اندازه گیری عملکرد بین المللی و پروتکل تأیید () - شبیه سازی انرژی درجه بندی شده - اندازه گیری و تأیید ( & )
کلمات کلیدی انگلیسی
پیش نمایش مقاله
پیش نمایش مقاله  تجزیه و تحلیل پارامترهای مصرف انرژی ساختمان و اندازه گیری صرفه جویی در انرژی و تایید با استفاده از نرم افزار eQUEST

چکیده انگلیسی

This study examines the Energy-Saving Performance Contract (ESPC) of an office building by applying IPMVP Option D in combination with the energy analysis model established for the building by eQUEST simulation software to calibrate energy consumption simulation results using actual electricity billing data. The rates of error between actual values and energy consumption simulation results from the calibrated and uncalibrated models are then explored to confirm the accuracy of the calibrated model. Finally, the calibrated model is used to examine the impact of energy consumption parameter changes on the overall energy consumption in a building. The results indicate that, compared to actual energy consumption, the mean bias error (MBE) and root mean square error (RMSE) for uncalibrated simulation results are 24.48% and 125,050, whereas the MBE and RMSE for calibrated simulation is 0.37% and 34,197. When lighting power density increases or decreases by 50%, overall energy consumption decreases by 30.78% or increases by 31.19%, respectively. Therefore, illumination density has the greatest impact on energy consumption. This study also recommends that accurate parameter settings be confirmed when using IPMVP Option D simulation verification to ensure a highly accurate building energy consumption model, thereby facilitating the Measurement and Verification (M&V) of energy savings.

مقدمه انگلیسی

In recent years, countries worldwide have implemented energy policies to achieve low-carbon energy-saving objectives, of which improving the efficiency of energy consumption while decreasing overall energy consumption is a crucial topic. Additionally, learning from the experience of foreign energy saving industries to support the development of energy service companies (ESCOs), the energy performance project model allows energy consumers to pay ESCOs for the cost of energy-saving projects through the energy efficiency created by the project, thereby creating a win-win situation. The US Department of Energy (DOE) has cooperated with the industrial community to develop a protocol for energy efficiency measurement and verification: the International Performance Measurement and Verification Protocol. By standardized M&V methods, the objective of this protocol is to confirm the energy efficiency attained through energy-saving measures and reduce the energy consumers’ doubts on energy efficiency [1]. This International Performance Measurement and Verification Protocol (IPMVP) is sponsored by the Efficiency Valuation Organization (EVO), a private, non-profit corporation. The IPMVP provides an overview of current best practice techniques available for verifying the results of energy efficiency, water efficiency, and renewable energy projects. The IPMVP provides four M&V method options: A–D. Option D is a type of numerical simulation that can improve M&V of building energy savings and evaluate in advance the effect of applying each energy-saving measure on a building's overall energy consumption [2]. Extensive research has focused on examining building energy consumption conditions. Zhu [3] used eQUEST simulation software models to analyze the effect of various energy-saving measures on building energy consumption conditions and rated the measures according to the Energy Star standard. Simulating community emergency service centers energy consumption conditions through eQUEST, Kim et al. [4] employed data mining to compare the original building's baseline energy consumption conditions with 12 HVAC options, 127 roof structures, 88 wall materials, and 12 building orientations and calculated the savings of efficient energy. They observed that HVAC had the greatest effect on building energy consumption, with an efficient energy annual savings of US$1507, and building orientation had the least effect on energy consumption, with an efficient energy annual savings of only US$11–US$17. Yu et al. [5] used eQUEST to research the impact of various parameters, such as building envelope shielding, external wall thermal insulation, external wall thermal emission, window/wall ratio, and glass type on air conditioner energy consumption in residential buildings. Their results showed that improvements in envelope shielding and external wall insulation could effectively decrease air conditioner energy consumption, with an energy savings rate of 11.31% and 11.55%, respectively. Sozer [6] argued that because rigorous regulations and limits had not been established, older hotels consumed extremely high levels of energy. Using eQUEST software simulation, Sozer examined passive designs that could effectively decrease building energy consumption, ultimately demonstrating that insulation, shielding, and window type can reduce heating and cooling energy consumption by 40%. Radhi [7] researched the building energy reduction effects of using insulation in building walls and showed that insulation can reduce building electricity use and CO2 emissions by approximately 40%. Santamouris et al. [8] installed a green roof system in a nursery school and employed theoretical simulation and empirical research to show that the system could effectively reduce cooling loads by approximately 6–49%. Florides [9] used TRYSNS software to research modern residential energy consumption and found that roof insulation measures were significantly effective in reducing cooling and heating loads. Pacheco et al. [10] introduced low-energy consumption building design parameters, including building orientation, building wall construction, building shields, glass classification, and passive heating and cooling mechanisms, for building designer reference. Gratia et al. [11] researched window blind size and color optimization and showed that during the summer, window blind optimization could reduce building air conditioner electricity use by 14.1%. Li et al. [12] showed that offices could reduce lighting power density energy consumption by 21.2% and air conditioner energy consumption by 6.9% using solar film coating and light control. Castleton et al. [13] examined green roof installation techniques and energy-saving potential for buildings. Phillip et al. [14] used TRACE600 to simulate commercial building energy consumption and researched 20 energy-saving measures that future engineers could use when designing air conditioning systems. Kawamoto et al. [15] evaluated the energy-saving potential of office equipment management at 3.5 TWh annually, or approximately 2% of Japan's annual commercial energy consumption. Tavares et al. [16] used VisualDOE™ simulation tools to conduct sensitivity analysis on wall structure and materials, window frames, and HVAC systems in government buildings. Yin et al. [17] used eQUEST to detail how double low-E windows with a solar film coating could effectively reduce the annual electrical use and peak demand in commercial buildings, showing that internal and external solar film coatings reduced cooling loads by 2.2% and 27.5%, respectively. Kim et al. [18] used IES VE energy analysis programming to study the impact of different exterior shading devices on the air conditioning load in residential buildings, demonstrating that exterior shading devices could effectively reduce air conditioning energy consumption in buildings.

نتیجه گیری انگلیسی

This study applied IPMVP's Option D and used the eQUEST simulation software to examine the energy consumption circumstances for an office building in Taiwan. When establishing the model, the accuracy of the energy consumption parameter settings must be confirmed, and the parameters must be calibrated to increase model accuracy if excessive errors occur between the simulated energy consumption and the actual values. Furthermore, the calibrated model can be used to examine the impact of energy consumption parameters on a building's overall energy consumption. The results are summarized in the following conclusions: 1. The baseline model energy consumption simulation showed that the yearly MBE and RMSE are 24.48% and 125,050, compared to the actual energy consumption. This is a low-accuracy model. After calibrating the occupancy, the lighting power density schedule, and the equipment power schedule independently, the yearly MBE and RMSE for these calibrated models are 27.46% and 136,667, 5.92% and 54,746, and 14.36% and 82,180, respectively. These results show that single parameter calibration is unable to effectively decrease simulation error. 2. After calibrating and combining the occupancy, lighting power density schedule, and equipment power schedule parameters, the calibrated model yielded simulation results showing that the yearly MBE and RMSE are 0.37% and 34,197, respectively. This is a highly-accurate model. These results show that energy consumption parameters must conform to actual circumstances to avoid excessive errors in the simulation results. 3. When occupancy changes from −50% to +50%, the rate of change in energy consumption is between −0.78% and 1.67%. This minor difference has a limited impact on the building's energy consumption. When lighting power density changes from −50% to +50%, energy consumption changes range between −30.28% and 31.19%. This has a significant impact on the building's energy consumption.