دانلود مقاله ISI انگلیسی شماره 139559
ترجمه فارسی عنوان مقاله

مطالعه تجربی در مورد کارآیی خاموش کردن سیستم اسپری هوا فشرده در آتش سوزی نفت

عنوان انگلیسی
Experimental Study on the Extinguishing Efficiency of Compressed Air Foam Sprinkler System on Oil Pool Fire
کد مقاله سال انتشار تعداد صفحات مقاله انگلیسی
139559 2018 10 صفحه PDF
منبع

Publisher : Elsevier - Science Direct (الزویر - ساینس دایرکت)

Journal : Procedia Engineering, Volume 211, 2018, Pages 94-103

ترجمه کلمات کلیدی
سیستم اسپری هوای فوم فشرده، رفع خستگی، آتش سوزی، نرخ استفاده از فوم مکانیزم خاموش شدن
کلمات کلیدی انگلیسی
compressed air foam sprinkler system; extinguishing efficiency; pool fire; foam application rate; extinguishing mechanism;
پیش نمایش مقاله
پیش نمایش مقاله  مطالعه تجربی در مورد کارآیی خاموش کردن سیستم اسپری هوا فشرده در آتش سوزی نفت

چکیده انگلیسی

In order to evaluate the impact of foam qualities and foam application rates on the extinguishing efficiency of compressed air foam sprinkler system on oil pool fire, a series of large-scale gasoline fire extinguishment experiments have been conducted under different expansion ratios and foam application rates. The consumed foam solution dosages to control and extinguish the pool fire have been calculated out respectively. The result showed that foam qualities significantly affect the extinguishing efficiency and burn back resistance performance of compressed air foam sprinkler system. The optimal expansion ratios of compressed air foam was about 10:1 comprehensive considering the extinguishing performance, re-ignition resistance, burn back protection and economical efficiency. It was found that as the foam application rate increases, the fire extinguishing and burn back protection performances of compressed air foam can be evidently improved. The most economical and efficient foam application rate on gasoline pool fire was 3.48 L/ (min· m2), and the minimum foam solution dosage to 90% control and entirely extinguish the fire were 0.99 L/ m2 and 2.38 L/ m2 respectively. The research results are vital to the engineering application of compressed air foam sprinkler system.